Safepower Modular SPM is based on modular architecture. Each 10-40 kVA UPS module is housed in a single 19” plug-and-play drawer with hot-swap capability. It is virtually a complete UPS. Single points of failure are thus eliminated (decentralised architecture). In the event a module needs to be replaced, it can be hot-swapped without affecting the operation of the other active modules. It’s easy to add power: the 3U-high plug-n-power  drawers can be hot-swapped allowing a vast vertical expansion (by populating the cabinet vertically) and horizontal expansion (by populating several columns).

 

SIEL16 CATALOGO UPS BR0673
SIEL16 CATALOGO UPS BR0674
 

 

Technical Data
Size in kVA 100 200 320 520 800 1040 1280 1560
FRAME SYSTEM
Max N° of UPS module 5x20k 5x40k 8x40k 13x40k 20x40k 26x40k 32x40k 39x40k
Dimension (WxDxH) mm 600x840x1400 600x860x1600 600x860x2000 1200x860x2000 3400x860x2000 4800x1100x2000
Total Weight (Kg) 270 375 582 892 2272 2476 2880 3400
MODULE
Size in kVA/kW at 40°C Size in kVA/kW at 40°C 40 /36
Dimension (WxDxH) mm 443x580x131 (3U)
Weight (Kg) 26 34
INPUT DATA
Nominal voltage Vac 380/400/415 Trifase Three-Phase + N
Power factor Power factor
Current distortion (THDI) ≤ 3%
OUTPUT DATA
Nominal voltage Vac 380/400/415 Trifase + N (selezionabile) Three-Phase + N (selectable)
Voltage regulation ±1% static; < ± 5% dinamic
Overload capacity 110% for 60mins; 125% for 10 min (on-line); 150% for 1 min (on-line); 1000% for 1 cycle (bypass)
Efficiency 96% (qualsiasi carico/any load); 99% (SES Mode)
GENERAL DATA
Battery range Adjustable 192 to 240 cells
Front panel Touchscreen display, mimic with LEDs plus an LCD display on each single UPS module
Standard communication
port
RS232, RS485, Modbus, dry contacts, 2x intelligent slots, Remote Emergency Power Off input, Diesel mode
input, Backfeed protection output
Altitude without dereting  
Standards CE – IEC EN 62040 1-2-3