HALLEY E represents the series of our product that has sold the most worldwide. It is a very reliable product with great flexibility. It is used mostly in the hospital and industrial environments. The 125kVA and 160kVA versions are often used for data processing centres and critical servers protection.
UPS power - kVA | 100 | 125 | 160 |
---|---|---|---|
Nominal input voltage • Vac | 380 • 400 • 415 (± 10%) | ||
Nominal output voltage - Vac | 380 • 400 - 415 ( ± 1% ) | ||
Nominal output power (0.8 PF) - kVA | 100 | 125 | 160 |
Output frequency· Hz | 50 / 60 | ||
Efficiency (AC÷AC) - % | >93 | ||
UPS amb ient tem p erat ure - C° | 0 - 40 | ||
Audib le noise level (acc. En50091) - dB |
<59 | ||
Battery test | Automatic every month / manual | ||
Rectifier bridge | SCR - 6 pulses | ||
Inverter bridge | IGBT (wit h isolation transformer) | ||
Overload capability | 125% for 10', 150% for 1 ', 200% for 100 ms | ||
Output harmonic distortion (THDV) | <2% | ||
Crest factor | 3:1 | ||
Dime nsionsWxDxH• mm | 815x820x1670 | ||
Walk-in | Adjustable from 5" to 30" | ||
Hold-off | Adjustable from 1" to 300" |