Thetys EVO
Due to its dual online conversion with inverter transformer, THETYS EVO 60 - 160 kVA offers the galvanic insulation between direct and alternate voltage as a standard, and also ensures excellent performance in terms of dynamic response. With the use of an IGBT rectifier with the innovative technology of sinusoidal absorp tion, it is able to achieve a high reduction of harmonics (THDI <3%) and a power factor of the absorbed input current close to one (>0,99). These characteristics make it highly compatible with the unit upstream from the UPS without having to install additional filters. Moreover, Thetys Evo addresses the need to save on the operating costs of the most advanced computer systems due to its compact size and efficient design, which enables it to achieve an efficiency exceeding 94%. The cabinet can be placed against a walland next to other electric panels without losing performance,due to its well-designed cooling system. The UPS is provided with a user -fr iendly intuitive interface, with m1m1c panel and led display, and includes a wide range of connectivity options which make the UPS easier to use and control in various installati ons. Finally, THETYS EVO is also available in parallel configurations to obtain redundancy and increase capacity, making it easy to install due to the parallel ready technology which comes standard on the unit .
Nominal output power (0.8 PF) - kVA | 60 | 80 | 100 | 125 | 160 |
---|---|---|---|---|---|
Nominal input voltage - Vac | 400 ( -20%/ + 15% ) ; 380/415 settabile | ||||
Nominal input current - A | 75 | 100 | 125 | 156 | 200 |
Input power factor | >0.99 | ||||
Input harmonics distortion (THDI) | <3% | ||||
Nominal output voltage - Vac | 380, 400, 415 ( ±1% ) | ||||
Efficiency (AC+AC) - % eco mode |
up to99 | ||||
Efficiency (AC+AC) - % | up to94 | ||||
UPS amb ient temperat ur e - C° | 0-40 | ||||
Audible noise level (acc.En50091) - dB | <60 | ||||
Battery test | Automatic every month / manual | ||||
Rectifier bridge | IGBT | ||||
Inverter bridge | IGBT(with isolati on tran sformer) | ||||
Overload capability | > 100°/o + 125% per 10 min., > 125% + 150% per 1 min., > 150% + 199%per 10 sec., a 200% per lOOms. | ||||
Output harmonic distortion (THDV) | <1% | ||||
Crest factor | 3:1 | ||||
DimensionsWxDxH - mm | 815 X 865 X 1705 | ||||
Walk-in | Adjustabl e from 5" to 30" | ||||
Hold-off | Adjustable from 1" to 300" |