Exchange - MTR

Print
Description

The Static Transfer Switch  (STS), based on a “break before make” technology, will transfer the load from one power source to another without causing any interruption of supply. It is available in the single phase verison (MTR) from 16A to 32A and in the Three-Phase version (Exchange) with 3 or 4 poles from 63A up to 1600A.

MTR:

  • Hot-swappable power electronic
  • Integrated standard manual bypass
  • 19” Rack
  • Standard communication RS232 and free contacts

 

EXCHANGE:

  • Integrated input, output and bypass breakers
  • Available in 3 or 4 pole version
  • Chassis version on request

 

SIEL16 CATALOGO UPS BR0673

 

Technical Data
Size in A 16 32 63 100 160 200 300 400 600 800 1200 1600
DATI INGRESSO / INPUT DATA
Nominal voltage 230 V+7- 20% 400 V + 20%- 35%
Nominal frequency (Hz) 50/60 ± 5%
Number of phases 1+N 3+N
OUTPUT DATA
Efficiency at In (%) >99 >98 >99 >98 >99
Mode of transfer Break Before Make
Overload 10 minutes 125%
Overload 1 minute 150%
Overload 10 seconds 200%
Overload 1 secondo 1000% 1500A 2400A 3000A 60000A 8000A 8000A 13000A
GENERAL FEATURES
Running mode Fixed priority/No priority (can be selected)
Electromagnetic compatibility
(CEI EN 62040-2)
A Class
Neutral sizing 1,5 In
Running temperature (°C) 0÷40
Communication interfaces Synoptic with LED - RS232
- free contacts port
MODBUS - TeleGlobal Service - SNMP Synoptic with LED
- RS232 - RS485 -
Synoptic with LED - RS232
- free contacts port
MODBUS - TeleGlobal Service - SNMP Synoptic with LED
- RS232 - RS485 -
Dimension (WxDxH) mm 483x480x88 800x830x1400 800x830x2000 800x830x2000 1350x1000x2000 2900x1000x2500
Standards CE – IEC EN 62310    IEC EN 62040-2

 

 

 