Safepower S
Safepower S UPS series, are suitable for all applicationsSafepower S UPS series, are suitable for all applicationswhere the protection of critical load are requested, fromthe simplest to the most complicated installations wherethe demand for reliability and maintainability is higherSafepower S is compatible with industrial installationsand most critical Information Technology (IT)thanks to the high levels of performance.
- Efficiency up to 94,5%
- Cos phi 0.9 output
- Input Power Factor at full load: 0.99
- Low voltage distortion <3%
- Design transformer-free
- Parallelable up to 4 units
- Cold start mode from battery
- EN50171 compliant
- Frequency converter mode setting
- Monitoring with SNMP, RS232, USB, modbus
Size in kVA | 10 | 15 | 20 | 30 | 40 |
---|---|---|---|---|---|
ELECTRICAL DATA | |||||
Active Power with PF from 0.9 inductive to 0.9 capacitive (kW) |
9 | 13,5 | 18 | 27 | 36 |
INPUT DATA | |||||
Nominal voltage Vac | 380/400/415 Three-Phase plus Neutral | ||||
Nominal frequency (Hz) | 50 / 60 | ||||
THDI (%) | ≤ 3 % | ||||
Power factor with full load | 0,99 pf | ||||
OUTPUT DATA | |||||
Nominal voltage Vac | 380/400/415 Three-Phase plus Neutral | ||||
Nominal frequency (Hz) | 50 / 60 | ||||
Static Stability | ± 1% | ||||
Restore within ± 1% In compliance with EN 62040-3, Class 1 | 20msec | ||||
Voltage distortion with linear load / with no linear load (EN 62040-3) |
≤ 1% / ≤ 3% | ||||
GENERAL DATA | |||||
Dimensions (WXDXH) mm | 250x828x868 | ||||
Max. weight without/with batteries inside (Kg) | 75/115 | 63/170 | 64/171 | 71/223 | 73 |
Cabinet protection degree | IP20 | ||||
Operating temperature (C°) | 0 ± 40 ºC | ||||
Standards | CE – IEC EN 62040 1-2-3 |