Safepower Evo HF series is capable of providing clean energy to the connected load, without interruption, regardless of the conditions of the supply network; ideal for the protection of computer networks, telecommunications and critical systems in general. Safepower Evo HF is available in models from 10 to 200 kVA, with double conversion on-line technology according to the VFI-SS-111, as defined by the IEC EN 62040-3. High performance components and technological solutions guarantee a total efficiency up to 96.5% (on-line mode double conversion) and >98% for operation ECO-MODE. The ability to supply loads is of the inductive type which capacitive and delivering the required active power (kW) required by the load
characterize the UPS in its market segment.
- High efficiency
- Cos phi 0.9 output
- Transformer free
- Parallelable up to 8 units
- EN50171 compliant
- Configurable frequency converter mode
- Monitoring via SNMP, RS232, RS485 Modbus
Size in kVA | 10 | 15 | 20 | 30 | 40 | 60 | 80 | 100 | 125 | 160 | 200 |
---|---|---|---|---|---|---|---|---|---|---|---|
ELECTRICAL DATA | |||||||||||
Active Power with PF from 0.9 inductive to 0.9 capacitive (kW) |
9 | 13,5 | 18 | 27 | 36 | 54 | 72 | 90 | 125 | 160 | 200 |
INPUT DATA | |||||||||||
Nominal voltage Vac | 380/400/415 Three-Phase plus Neutral | ||||||||||
Nominal frequency (Hz) | 50 / 60 | ||||||||||
THDI (%) | ≤ 3 % | ||||||||||
Power factor with full load | 0,99 pf | ||||||||||
OUTPUT DATA | |||||||||||
Nominal voltage Vac | 220/230/240 Singlephase |
380/400/415 Three-Phase plus Neutral | |||||||||
Nominal frequency (Hz) | 50 / 60 | ||||||||||
Static Stability | ± 1% | ||||||||||
Restore within ± 1% In compliance with EN 62040-3, Class 1 |
20msec | ||||||||||
Voltage distortion with linear load / with no linear load (EN 62040-3) |
≤ 1% / ≤ 3% | ||||||||||
CARATTERISTICHE GENERALI / GENERAL DATA | |||||||||||
Dimensions (WXDXH) mm | Dimensions (WXDXH) mm | 500x850x1600 | 500x850x1600 | 840x1050x1900 | |||||||
Max. weight (Kg with batteries inside * ) |
305* |
315* |
320* |
335* |
345* |
190 |
200 |
220 |
250 |
450 |
460 |
Cabinet protection degree | IP20 | ||||||||||
Operating temperature (C°) | 0 ± 40 ºC | ||||||||||
Standards | CE – IEC EN 62040 1-2-3 |